| ASHRAE # | Trade Name | Manufacturer | Replaces | Type | Composition (wt%) | GWP (100 yr) | Recommended Lubricant |
Applications |
|---|---|---|---|---|---|---|---|---|
| R-410A | Forane® 410A | Arkema | R-22 | HFC Near-azeotropic blend |
R-32 - 50% R-125 - 50% |
2,088 | POE | Replacement for R-22 in smaller size chillers, and residential and light commercial A/C systems. Never use as a retrofit for R-22 equipment. |
| Puron® Suva® 410A Genetron® AZ-20 Klea® 410A |
Carrier DuPont Honeywell Mexichem |
|||||||
| R-427A | Forane® 427A | Arkema | R-22 | HFC Zeotropic blend |
R-32 - 15% R-125 - 25% R-143a - 10% R-134a - 50% |
2,138 | MO or AB (with oil separator) POE |
Recommended/retrofit for R-22 in DX systems. Used in A/C, medium, and low temperature systems. |
| R-407A | Forane® 407A | Arkema | R-22 | HFC Zeotropic blend |
R-32 - 20% R-125 - 40% R-134a - 40% |
2,107 | POE | Replacement/retrofit for R-22 DX systems. Used in medium and low temperature refrigeration. |
| Suva® 407A Klea® 407A |
Dupont Mexichem |
|||||||
| R-407C | Forane® 407C | Arkema | R-22 | HFC Zeotropic blend |
R-32 - 23% R-125 - 25% R-134a - 52% |
1,774 | POE | Replacement/retrofit for R-22 DX systems. Used in residential A/C, medium, and low temperature systems. |
| Suva® 407C Genetron® 407C Klea® 407C |
Dupont Honeywell Mexichem |
|||||||
| R-134a | Forane® 134a | Arkema | R-12 | HFC Single component fluid | R-134a - 100% | 1,430 | POE PAG (auto) |
Replacement/retrofit for R-12 and R-500 systems. Recommended retrofit for R-12 automotive A/C systems. |
| Suva® 134a Genetron® 134a Klea® 134a |
Dupont Honeywell Mexichem |
|||||||
| R-404A | Forane® 404A | Arkema | R-502 R-22 R-402A R-408A |
HFC Near-azeotropic blend |
R-125 - 44% R-143a - 52% R-134a - 4% |
3,922 | POE | Replacement/retrofit for R-502 and R-22. Used in medium and low temperature refrigeration systems. |
| Suva® 404A Genetron® 404A Klea® 404A |
Dupont Honeywell Mexichem |
|||||||
| R-507A | Forane® 507A | Arkema | R-502 R-22 R-402A R-408A |
HFC Azeotropic blend |
R-125 - 50% R-143a - 50% |
3,985 | POE | Replacement/retrofit for R-502 and R-22. Used in medium and low temperature refrigeration systems. |
| Suva® 507A Genetron® AZ-50 Klea® 507A |
Dupont Honeywell Mexichem |
|||||||
| R-22 | Forane® 22 | Arkema | HCFC Single component fluid |
R-22 - 100% | 1,810 | MO AB |
Used in A/C, medium, and low temperature systems. | |
| Freon® 22 Genetron® 22 |
Dupont Honeywell |
|||||||
| R-408A | Forane® 408A | Arkema | R-502 | HCFC Near-azeotropic blend |
R-125 - 7% R-143a - 46% R-22 - 47% |
3,152 | MO AB POE |
Recommended retrofit for R-502 systems. Used in medium and low temperature systems. |
| Suva® 408A Genetron® 408A |
Dupont Honeywell |
|||||||
| R-409A | Forane® 409A | Arkema | R-12 R-500 |
HCFC Zeotropic blend |
R-22 - 60% R-124 - 25% R-142b - 15% |
1,585 | MO AB POE |
Recommended retrofit for R-12/R-500 stationary DX systems. Used in medium and low temperature systems. |
| Suva® 409A Genetron® 409A |
Dupont Honeywell |
|||||||
| R-123 | Forane® 123 | Arkema | R-11 | HCFC Single component fluid |
R-123 - 100% | 77 | MO AB POE |
Used in Centrifugal Chillers. Scheduled for phase-out. |
| Suva® 123 Genetron® 123 |
Dupont Honeywell |